Electrical Ratings
Type: Soft-starter
Main operating voltage (motor supply): 208 … 600 V AC
Rated operational current (Ie): 18 A
Rated operational power (in-line connection):
~4 kW at 230 V
~7.5 kW at 400 V
~11 kW at 500 V
Control supply voltage (Us): 100 … 250 V AC, 50/60 Hz
DC control circuit supply option: 24 V DC
Frequency: 50/60 Hz
Starting Performance
Starting capacity: 4×Ie for 10 s
Ramp-up time: Adjustable 1 … 30 s
Initial start-voltage: 30 … 70 %
Current-limit function: 1.5 … 7 × Ie
Kick-start function: Yes (for high-load starts)
Protection & Monitoring
Built-in electronic overload protection
Locked-rotor protection
Under-load/dry-run detection
End-of-load (EOL) detection
Thermal protection
Fault diagnostics
Bypass relay (integrated)
Control & Communication
Hard-wired Start / Stop / Reset
Optional Modbus RTU
Optional fieldbus gateways
Relay outputs for Run, Bypass, Fault, Overload
Analog output: 4–20 mA