Motor output power:
• 37.0 kW (≈ 50 hp)Rated supply voltage:
380–480 V AC, 3-phase
(operating supply limits ~ 323–528 V)Continuous / Line current (motor):
• ~ 68.9 A at 380 V
• ~ 54.4 A at 480 VApparent power rating:
• ~ 52 kVA at 380 VOutput frequency range:
0.5 – 200 HzSpeed control / Speed range:
Speed range approx. 1 : 10 (depending on motor and setup)Switching / PWM frequency:
Nominal switching frequency ~ 8 kHz
Adjustable switching frequency 8–16 kHz (with derating when above nominal)Transient / Overload / Overcurrent capability:
• Maximum transient current: ~ 86.9 A (for 60 s)
• Continuous output current rating (after derating if applicable) ~ 79 AProtection rating / Mounting style:
IP21 (standard enclosure for indoor panel / HVAC-drive mounting)
Mounting: vertical orientation, panel-mount type — designed for HVAC / fluid-management installationsIntegrated EMC filter:
Yes — built-in EMC filter (Class C2) for reduced harmonics / EMI, avoiding mandatory external line chokes under typical install conditions
Schneider ATV212HD37N4 37 kW, Altivar Process ATV212 New
This product needs minium 3 business days prepare time.
ATV212HD37N4